Protection CTs and VTs Guide

How current and voltage transformers feed protection: accuracy classes, burden, knee-point, saturation, ratio selection, polarity, grounding and common wiring faults that disable protection.

In short. Relays see the system only through CTs and VTs. If a CT saturates, is wired with the wrong polarity or is open-circuited, protection can fail to operate or trip wrongly. Selecting the correct class, ratio and burden is as important as setting the relay.

CT basics

Saturation

During a fault with large current or DC offset, the CT core may saturate and the secondary current becomes distorted. Check that the CT will not saturate before the relay operates at the maximum fault current, with margin for DC offset.

VT basics

ItemCTVT
ConnectionIn series with the circuitIn parallel with the circuit
Secondary must not beOpen-circuited (dangerous voltage)Short-circuited (overload and damage)
Main riskSaturation, polarity, open circuitFuse loss, wrong phasing

Selection steps

  1. Choose the primary ratio from load and fault current.
  2. Calculate the burden of relays and cabling.
  3. Check the accuracy limit or knee-point for the maximum fault.
  4. Specify class by function: overcurrent, differential, REF, metering.
  5. Define polarity and earthing of the secondary circuits (one point only).

Commissioning checks

Illustrative example

A generator panel uses 1000/1 A CTs with a relay burden and cable giving a total burden of a few ohms. Calculation shows the CT would saturate at the maximum fault current, so a CT with a higher knee-point or a shorter cable run, or heavier conductors, is chosen. Without this check, the relay might trip too slowly or not at all.

Why CTs decide whether protection works

A relay sees only what the current and voltage transformers deliver. Wrong ratio, polarity, class or saturation turns a good relay into a wrong one.

CT selection parameters

ParameterMeaning
RatioPrimary to secondary current; primary rating above maximum load
Accuracy classMetering classes for billing, protection classes (such as 5P or 10P) for relays
Accuracy limit factorMultiple of rated current up to which accuracy holds
Burden (VA)Load of relay plus wiring on the secondary
Knee-point voltageFor class X CTs used in differential schemes

Saturation check (illustrative)

If a CT is rated 1000/1 A, 10P20, at 15 VA, and the actual burden is 20 VA, accuracy at 20 times rating can be lost. Reduce burden by shortening leads, using larger conductors or choosing a 1 A secondary, or select a larger CT.

Safety rules

VT issues

  1. Fuse or MCB failure on a VT secondary can mimic undervoltage. Add VT supervision.
  2. Check ratio, burden and phase sequence.
  3. For generators, VT location relative to the breaker affects protection and sync functions.

Testing

Ratio, polarity, magnetisation curve and burden measurements are routine commissioning tests. See injection testing.

Common mistakes

What to send us

Send the CT and relay data. Send your application details. See also differential protection.

Questions engineers ask

Why must a CT secondary never be open?

An open secondary can develop dangerously high voltage and damage the CT.

What is CT knee-point?

The voltage at which the core starts to saturate, important for differential and REF schemes.

Can one CT serve protection and metering?

Not reliably. Use separate cores or CTs.

What if a VT fuse blows?

Voltage-based protection may misbehave, so relays include VT supervision.

This guide gives general principles. CT specification needs relay and fault data.