Reddy GeneratorsREDDY GENERATORSThe dependable power professionals

Reverse Power and Generator Protection Guide

What reverse power, loss of excitation, overload and other generator protections do, why a motoring generator can damage its engine, and how to set and test these functions in parallel systems.

In short. A generator running in parallel can be driven by the system instead of driving it. Reverse power protection detects this “motoring” and trips before the engine or turbine is damaged. It sits within a wider set of generator protections.

Reverse power

If the engine loses fuel or its governor fails while the breaker is closed, the alternator draws real power and spins the engine as a motor. A diesel engine can tolerate this only briefly. The reverse power relay measures active power flow into the generator and trips after a short delay. Settings depend on the engine’s motoring power, usually a few percent of rating, so the relay needs sensitive, accurate measurement.

Other generator protections

FunctionDetects
Loss of excitation (40)Field loss, which draws large reactive power from the system
Overload / overcurrent (51)Thermal or short-circuit conditions. See overcurrent
Negative sequence (46)Unbalanced loading. See negative sequence
Stator earth fault (51G/REF)Winding earth faults
Differential (87G)Phase faults in the stator
Over/under voltage and frequencyAbnormal operation. See voltage and frequency
Overspeed, low oil pressure, high temperatureEngine protections handled by the controller

Setting reverse power

  1. Find the engine’s motoring power from the manufacturer.
  2. Set the pickup below this, with allowance for measurement error.
  3. Choose a time delay long enough to ride through synchronising swings and short disturbances, short enough to protect the engine.
  4. Verify with a controlled test when the engine is at low load.

Where it matters

Illustrative example

Two generators share a bus. One loses its fuel supply and the governor output falls to zero, while its breaker stays closed. The healthy unit begins to drive the failed one. The reverse power relay sees power flowing in and trips the breaker after a few seconds, and the healthy unit continues to carry the load.

What reverse power means

When a generator running in parallel loses its fuel supply or its prime mover fails, it stops delivering power and starts absorbing real power from the system, motoring its engine. This reverse power can damage the prime mover and may be hazardous.

Typical reverse power levels

Prime moverMotoring power (order of magnitude)Consequence
Diesel engineSeveral percent up to around 15 percent of rating, depending on engineMechanical stress, fire risk from unburnt fuel
Gas turbineHigher percentagesGearbox and shaft stress

Use the engine maker’s motoring data for settings.

Setting approach

  1. Set pickup below the engine’s motoring power but above measurement error and transient swings.
  2. Add a time delay to avoid tripping during synchronising or load transfer transients.
  3. Trip the generator breaker and shut down the engine.

Other generator protections in the same panel

Utility parallel operation

When a generator runs in parallel with the grid, reverse power can also mean export to the utility. Many utilities forbid export or require specific protection. Check agreements and use the correct relay function and settings.

Testing

Inject a reverse power signal and confirm the trip, time and shutdown action. Record results. Test again after control changes.

Common mistakes

What to send us

Send the generator and relay data. Send your application details. See also relay architecture.

Questions engineers ask

Is reverse power needed for a single standby set?

No, since nothing can drive it. It is for parallel operation.

What happens without it?

A motoring engine can overheat or suffer damage and fuel-less running problems.

How is it tested?

By secondary injection and a controlled on-site check.

Does it replace loss-of-excitation protection?

No. They detect different problems.

This guide gives general principles. Settings need engine and relay data.

CallWhatsAppEnquire