Generator Fuel Tank and Runtime Guide

How to size a generator fuel tank for a target runtime: consumption, usable volume, reserve, day tank versus bulk storage, resupply planning and safety and regulatory points to check.

In short. Runtime equals usable fuel divided by consumption rate. Size the tank for the outage you plan to ride through, allow for unusable volume and a reserve, and plan resupply for longer events. Fuel storage also brings safety, spill and regulatory requirements that must be checked locally.

The calculation

Runtime (h) = Usable fuel (L) ÷ Fuel rate (L/h)
Tank volume (L) = Fuel rate × Target hours ÷ Usable fraction

Usable fraction accounts for fuel below the pickup, tank margins and a deliberate reserve. A common allowance is 80 to 90 per cent, but check the tank design.

Worked example (illustrative)

A set burns about 77 litres per hour at its typical load. The site wants 24 hours of runtime and a usable fraction of 0.85. Tank volume = 77 × 24 ÷ 0.85 ≈ 2,174 litres. A 2,500-litre tank is a sensible standard size, giving about 27 hours of usable runtime at that load. At full load the consumption is higher, so runtime would be shorter. Check both the typical and the worst-case loads. See fuel consumption.

Tank arrangements

TypeUseNotes
Base tank (under the set)Common for small to medium setsCompact; runtime limited by size
Day tankSmall tank near the engine, fed from bulkNeeds transfer pumps and level control
Bulk tankLarger storage, above or below groundRules on location, bunding, venting
Mobile or rental tankExtra runtime for eventsPlanned connection and transfer

See fuel tank sizing and rental fuel tanks.

Design points

Planning for longer events

For outages beyond the tank’s runtime, you need resupply: a contract with a fuel supplier, with response time guarantees, access to the site and a safe way to refill while running. Consider how a regional disaster may disrupt supply. A common approach is to plan tanks for a target runtime and a resupply agreement for beyond.

Tank size from runtime

Required usable fuel (L) = consumption (L/h) × required hours × reserve factor

Worked example (illustrative)

A 500 kVA set at 75 percent load burns around 85 L/h. Required autonomy 24 hours with a 10 percent reserve: 85 × 24 × 1.1 ≈ 2,244 litres usable. Allow for unusable bottom volume and expansion space, so the tank might be rated 2,500 to 2,700 litres. Check that the tank is installed and licensed under the applicable rules for storing diesel.

Design aspectNote
Day tankSmall tank near the engine fed by a transfer pump
Bulk tankLarger tank with transfer pumps and a backup
Fuel qualityWater drain, filtration, polishing
Transfer pumpDuplicate pumps and manual option for critical sites
Spill containmentBund and venting as per local rules

Refuelling logistics

Autonomy is the tank plus the realistic delivery time during an emergency. During floods or area-wide outages, delivery may be delayed, so confirm supplier arrangements.

Fuel ageing

Stored diesel degrades over months. Rotate stock, test and polish where needed.

See fuel consumption guide and emergency and standby architecture.

Common mistakes

What to send us

Send the target runtime, the generator model and space for tanks. Send your application details.

Questions engineers ask

How many hours of fuel should I store?

It depends on your outage risk and resupply options. Many critical sites plan for a day or more, with resupply for beyond.

How long can diesel be stored?

It depends on conditions and treatment. Sample and test it regularly, and polish or replace it as needed.

Do I need a day tank?

For larger bulk storage, usually yes, to feed the engine safely and consistently.

Are there rules for storing fuel?

Yes. Quantities, location, bunding and licensing are regulated locally. Check with the authorities.

Figures are illustrative. Fuel storage must comply with applicable regulations.