Static Transfer Switch Systems

How static transfer switches move critical loads between two sources within milliseconds, where they fit in A/B distribution, key ratings and the failure modes to design out.

In short. A static transfer switch (STS) uses power electronics, not mechanical contacts, to move a load from one source to another in milliseconds. It gives single-corded loads access to two sources and protects against loss of one path. Because every load passes through it, the STS itself must be carefully designed and maintained.

What it does

The STS monitors a preferred and an alternate source. If the preferred source goes out of tolerance, thyristors switch the load to the alternate source, usually in a fraction of a cycle to a few milliseconds. To avoid large current surges, the two sources should be synchronised, normally by being fed from the same upstream system or by UPS inverters locked together.

STS versus ATS

AspectStatic transfer switchAutomatic transfer switch
TechnologyThyristorsMechanical contactor or breaker
Typical transfer timeMillisecondsTens to hundreds of milliseconds or more
Typical useBetween two UPS or clean sourcesBetween utility and generator
Heat lossesHigher, needs coolingLow

They are complementary. See ATS, STS and UPS coordination.

Where it sits in the system

Key specifications to check

Failure modes to design against

Worked illustration

Two 300 kVA UPS systems feed a 200 kVA group of single-corded loads through an STS. The STS is rated 400 A at the system voltage. On failure of UPS A, the STS moves to UPS B. If the downstream circuit includes a transformer, the inrush on transfer might reach several times rated current for a few cycles. The designer checks that UPS B can supply the inrush without tripping, or adds a transformer arrangement that limits it.

Maintenance

The STS needs a maintenance bypass so it can be serviced without dropping load. Test transfers periodically, check cooling, and review alarm history. Keep spares of fans and control boards.

What a static transfer switch does

An STS uses thyristors to move a load between two AC sources in about 4 to 8 milliseconds, fast enough that most IT power supplies see no interruption. It does so only if the two sources are in sync and within tolerance.

FeatureSTSATS
Transfer time4 to 8 msTens of ms to seconds
Switching elementThyristorsContactor or breaker
UseBetween two UPS or sources in syncBetween utility and generator
LossesContinuous small loss in thyristorsNegligible

Transfer logic

  1. Preferred source selected.
  2. If preferred source goes out of tolerance, check alternate source is in tolerance and in sync.
  3. Transfer, with back-feed protection that stops the load feeding the failed source.
  4. Retransfer when the preferred source is restored, normally after a delay.

Design points

Single point of failure

An STS itself is a single device between two sources. Use redundant STS or place STS near loads to limit what a failure affects. See transfer coordination.

Common mistakes

What to send us

Send the load, the sources and the single-corded devices involved. Send your application details. See also dual-cord and single-cord loads.

Questions engineers ask

Is an STS a single point of failure?

It can be. Design with a maintenance bypass and consider redundant STS units for the most critical loads.

Why must the two sources be synchronised?

If they are out of phase, a transfer can cause current surges and a voltage disturbance.

Can an STS replace an ATS?

No. An STS suits clean, synchronised sources, while an ATS typically moves between utility and generator.

What happens if the load has a fault when the STS transfers?

It may transfer the fault to the alternate source. Downstream protection must clear it quickly and selectively.

This guide gives general principles. Ratings and settings should be taken from manufacturer data and a protection study.