Critical-Power Requirement to Architecture Selection Guide

A guide to choosing a critical-power architecture from the requirement: outage tolerance, redundancy, maintainability and site constraints, mapped to the sources and topologies that fit.

In short. Start from what the site must tolerate, not from equipment. Outage tolerance decides whether UPS is needed; the failure to survive decides the redundancy; the need to maintain while live decides the paths; fuel and outage duration decide the energy source. This guide maps requirements to architectures and points to detailed pages.

Step 1: Outage tolerance

ToleranceImplicationGo to
NoneUPS or battery bridging, STS or dual pathUPS architecture
SecondsStandby generator with ATSstandby generators
Minutes to hoursManual or staged recovery, rental backupemergency rental power

Step 2: Failure to survive

Must surviveUsual architecture
Utility outage onlyN generator with ATS
One equipment failure or one maintenanceN+1
Failure during maintenanceN+2 or 2N
Loss of a whole system, room or path2N, separated
Regional or long outageFuel storage, resupply, island capability

See redundancy architectures.

Step 3: Maintainability

If equipment must be serviced without shutting the load, add isolation, a second path and spare capacity. See concurrent maintainability.

Step 4: Energy and duration

Step 5: Constraints

Step 6: Verify

  1. Check single points of failure and common-cause failures.
  2. Run protection and fault-level studies for every configuration.
  3. Plan integrated testing.

Worked example of the thinking

A manufacturing plant has a 1.2 MW process with a 30-second ride-through, a 40 kW control and IT load with no tolerance, and an expected outage of up to 24 hours. The mapping: UPS for the 40 kW, with 10 minutes of battery; N+1 generators (three of 600 kW) for the process, with fuel for 24 hours plus margin; automatic transfer and staged restart for the large motors; manual shedding of comfort loads. The architecture came from tolerance, failure and duration, in that order. A different plant with the same load but a 2N requirement would end up with a different design.

Where to go next

From requirement to architecture

RequirementArchitecture to consider
Short outage acceptable (tens of seconds), life-safety loadsStandby generator with ATS, readiness regime
No interruption for IT or control loadsUPS plus generator
Generator failure must not cause an outageN+1 generators
UPS failure or maintenance must not cause an outageN+1 modular UPS or two UPS systems
Any single path failure or maintenance with zero interruption2N or A/B distribution
Single-cord devices in A/B designRack STS
Long islanded operationMulti-DG plant with fuel autonomy, microgrid controller
Cost reduction and resilience togetherBESS with defined reserve
Old facility, cannot stopStaged brownfield modernisation with rental bridging

Questions that settle the design

  1. What does an hour of outage cost?
  2. Which loads tolerate which interruptions?
  3. How long must the site run without the grid?
  4. Can it be maintained without outage?
  5. Who operates it, and how well trained?

Principle

Choose the least complex architecture that meets the stated target, and prove it by test. Redundancy needs independent failure paths.

For help, use the application engineering enquiry. See resilience architecture.

Common mistakes

What to send us

Send your outage tolerance, loads, site constraints and risk targets. Send your application details.

Questions engineers ask

Where do I start if I do not know my requirement?

Begin with a load list and ask what happens to each load if power is lost for one second, a minute and an hour.

Is there one architecture that fits all sites?

No. The right design depends on tolerance, failure targets, duration and constraints.

Do I need 2N?

Only if you must survive the loss of a whole system or keep full redundancy during maintenance.

How do I check the final design?

By single-point-of-failure review, studies for protection and capacity, and integrated testing.

This guide gives general principles. Final design needs a site-specific engineering review.