Multi-Generator Capacity and Number of Generators

How to decide how many generators a site needs and in what sizes: load profile, redundancy, step handling, part-load efficiency, maintenance and growth, with a worked comparison of options.

In short. The number and size of generators is a trade-off between redundancy, efficiency at partial load, capability to take steps, space, cost and growth. More, smaller units give flexibility and resilience; fewer, larger units cost less and are simpler. Decide from the load profile and the redundancy target, then compare options side by side.

Inputs you need

How the arithmetic works

Units for N = round up (Design load ÷ Unit usable capacity)
Units for N+1 = Units for N + 1

Usable capacity is the unit’s rating after derating and target loading. Redundancy means the remaining units must carry the critical load with one unit out.

Option comparison (illustrative)

Design load: 1,800 kW; usable capacity per unit is taken as the full kW rating for simplicity.

OptionInstalledWith one unit outNotes
2 × 1,000 kW (N+1 not met)2,000 kW1,000 kWOnly 55 per cent covered after a failure
3 × 1,000 kW (N+1)3,000 kW2,000 kWCovers 1,800 kW; units run at about 60 per cent
4 × 600 kW (N+1)2,400 kW1,800 kWExactly covered; lower installed capacity
5 × 500 kW (N+1)2,500 kW2,000 kWBetter part-load; more units to maintain

The 4 × 600 kW option meets N+1 with the least installed capacity but leaves no margin for growth or derating. In practice, the usable capacity per unit would be lower than the rating, so more capacity would be needed.

Other factors

Same-size or mixed

Identical units simplify load sharing, spares and maintenance. Mixed sizes can match a wide load range, such as a small unit for light load and large units for peaks, but need careful control. See operating combinations and dispatch.

How many sets, and what size

For a design load L and a unit rating P, the number of sets needed to carry the load is the roundup of L ÷ P. Redundancy adds sets.

OptionSets for 1,500 kW critical loadComment
One 1,750 kW set1No redundancy
Three 500 kW, N3No spare
Four 500 kW, N+14Survives one failure
Three 750 kW, N+13 (2 needed)Larger units, fewer sets
Five 400 kW, N+15 (4 needed)Finer granularity, better light-load efficiency

Trade-offs

  1. More, smaller sets give finer matching and lower redundancy cost per unit, but more maintenance and more paralleling.
  2. Fewer, larger sets are simpler but each failure removes a larger share.
  3. Fault level rises with the number of sets in parallel.

Light-load operation

At night load might be 400 kW. With four 500 kW sets, running one at 80 percent is healthy; running all four at 20 percent is not. Load-dependent start and stop avoids this.

Verification

Check the largest motor start with N−1 sets running, not with all of them. See N+1, multi-DG capacity studies and redundancy capacity guide.

Common mistakes

What to send us

Send your load profile, redundancy target and space available. Send your application details. See also multi-DG capacity and N+1 studies.

Questions engineers ask

How do I choose between three large and four small generators?

Compare total installed capacity, capacity with one unit out, part-load efficiency, space, cost and maintenance complexity for your load profile.

Does N+1 mean one extra generator?

It means capacity for the load with one unit out. With uneven sizes, that is not necessarily one extra unit of the same size.

Can I add generators later?

Yes if the bus, controls, fuel and space were designed for it.

Is paralleling necessary?

For shared load and redundancy on one bus, yes. Separate units on separate loads do not need it but give less flexibility.

Figures are illustrative. Final selection needs a load study and manufacturer data.