How online double-conversion UPS works: rectifier, inverter, battery and bypass paths, efficiency modes, input window, harmonics, generator compatibility and when online is the right topology.

In short. An online UPS continuously converts input AC to DC and back to AC, so the load always runs from the inverter with no transfer time on mains failure. It isolates the load from the supply and suits critical equipment, at the cost of efficiency and heat.

Power path

Input → rectifier/charger → DC bus with battery → inverter → output. Static bypass is the alternative path. On mains failure the battery feeds the DC bus; the load sees no break.

Characteristics

FeatureEffect
Zero transfer timeNo break on mains failure
Output regulationVoltage and frequency regulated
EfficiencyLower than line-interactive; eco modes can raise it
HeatLosses become room heat; input = output ÷ efficiency
Input harmonicsRectifier type decides

Input window

An online UPS tolerates input voltage variation within a window without using the battery. A narrow window on a weak supply drains the battery. A stabiliser upstream can help. See stabiliser vs UPS.

Generator compatibility

See UPS and DG integration.

Modes of operation

  1. Normal double conversion.
  2. Battery mode on mains failure.
  3. Bypass on overload or fault.
  4. Eco mode where used, with clear understanding of the transfer behaviour.

Illustrative example

A trading office uses an online UPS for servers. A mains drop to zero causes no interruption; the generator starts and takes over, the rectifier walks in, and the battery recharges.

Efficiency and heat in detail

Input power = Output power ÷ Efficiency

A 20 kW load on a UPS of 94 percent efficiency draws about 21.3 kW; the difference of about 1.3 kW is heat in the room. At 90 percent efficiency, losses rise to about 2.2 kW. Over a year of continuous running, the energy lost is considerable, which is why efficiency at your typical load, not only at full load, should be checked in the datasheet.

Eco mode

In eco mode, the load runs on bypass while the supply is good, and the inverter takes over when it is not. Efficiency improves, but there is a short transfer, and the load sees the quality of the bypass supply meanwhile. Consider this carefully for critical loads and test the transfer time.

Input power factor and harmonics

Rectifier typeInput current distortionGenerator impact
Six-pulseHigh, needs filterMore voltage distortion
Twelve-pulseLowerBetter
Active front end (IGBT)Low, near unity power factorBest

Battery integration

See batteries.

Failure modes

FailureResult
Inverter faultLoad transfers to static bypass
Rectifier faultBattery supports until depleted
Battery faultNo ride-through
Fan or cooling faultThermal shutdown

Design the system so each failure leads to a known, acceptable state, and alarm it. Test those states.

The master engineering question

Is the load critical enough to justify double conversion losses, or would a simpler topology suffice?

What to send us

Send load list and room details. Send your application details.

Questions engineers ask

Is online UPS always best?

For critical loads, yes; for others, consider cost and heat.

What is eco mode?

The load runs on bypass when input is good; efficiency rises with some risk trade-off.

Why does it run hot?

Conversion losses.

Does it clean harmonics?

It isolates the load but its input may produce harmonics.

Values are illustrative. Use manufacturer data.