Harmonics and Harmonic Mitigation

What harmonics are, how drives, UPS and LED loads create them, effects on transformers, neutrals and generators, how to measure THD, and how filters and reactors reduce them.

In short. Harmonics are currents and voltages at multiples of the supply frequency, created by nonlinear loads. They heat transformers, cables and neutrals, distort voltage and upset generators. Measure first, then mitigate with reactors, filters or better equipment choice.

Physics to effect

Nonlinear load → distorted current → current flows through source impedance → distorted voltage → heating, nuisance trips, resonance. Generators have higher source impedance than the grid, so the same load distorts a generator more. See harmonics and THD.

Common sources

Effects

EquipmentEffect
TransformersExtra heating; derate or use K-rated
NeutralsTriplen harmonics add in the neutral
CapacitorsResonance risk. See APFC
GeneratorsVoltage distortion and rotor heating
ElectronicsMis-operation and trips

Mitigation options

  1. Line reactors or DC chokes on drives.
  2. Passive filters tuned for dominant harmonics.
  3. Active harmonic filters for varying spectra.
  4. Multi-pulse or active-front-end rectifiers.
  5. Oversizing or derating the source.

See harmonic studies and filter studies.

Measure

Log current and voltage THD and the spectrum at the point of common coupling and at the generator. Compare against agreed limits.

Illustrative example

A site with many drives sees generator voltage THD rise during runs. Line reactors on the drives and an upstream filter reduce THD and stop random trips. Before-and-after measurements prove the result.

Measuring harmonics properly

  1. Use an analyser rated for harmonic measurement up to a suitable order.
  2. Measure at the point where the generator or transformer connects to the loads.
  3. Record at light, typical and peak load.
  4. Record voltage and current distortion separately.
  5. Note the dominant orders, such as the 5th, 7th and 11th for six-pulse rectifiers.

Why generators suffer more

Voltage distortion ≈ Harmonic current × Source reactance at that harmonic

A generator’s subtransient reactance is much higher than a transformer’s, so the same harmonic current produces more voltage distortion. For a set feeding mostly drives or UPS, the voltage can be distorted enough to upset other loads. This is why generator sizing for nonlinear loads often includes extra margin or filtering. See UPS and nonlinear loads.

Mitigation comparison

MethodStrengthLimitation
Line reactorsSimple, low costPartial reduction
Passive tuned filterTargeted at specific ordersNeeds study; can resonate
Active filterAdapts to varying spectrumHigher cost
Multi-pulse or active front endReduces at sourceEquipment choice at purchase
Oversized sourceLowers source impedance effectCost and space

Neutral and triplen harmonics

Single-phase electronic loads produce third-harmonic currents that add in the neutral instead of cancelling. In some offices the neutral current can exceed the phase current. Size neutrals and transformers with this in mind.

Verification

After mitigation, repeat measurement under comparable load. Keep a before-and-after table. Compare against the limits agreed with the utility or defined in the standard you follow.

The master engineering question

Which loads produce the harmonics, which equipment suffers, and where is the best place to treat them?

What to send us

Send single-line diagram and measurements. Send your application details.

Questions engineers ask

Is THD always bad?

High THD at a weak source can harm; small at a stiff source may be fine.

Do stabilisers fix it?

No.

Why is a generator more sensitive?

Higher source impedance converts current distortion to voltage distortion.

Passive or active filter?

Depends on spectrum stability and budget; study it.

Values are illustrative. Follow applicable standards.